Steel Tank Surface Piping Iron-Manganese-Arsenic Filter Systems

Steel Tank Surface Piping Iron-Manganese-Arsenic Filter Systems

  • EXPLANATION

    AQUALINE IRON, MANGANESE FILTERS

    Thanks to Aqualine Iron, Manganese filters special minerals; up to 5ppm in water  It can reduce the amount of iron and manganese to drinking and utility water standards (Fe=0.2 ppm - Mn= 0.05ppm). There is no need for any extra regen material for these special minerals. It also removes hydrogen sulfide, methane, free carbon dioxide and high concentration organic residues in water.

     

    AQUALINE ARSENIC FILTERS

    Arsenic is one of the most abundant elements in nature with a feature between metal and nonmetal. It is a carcinogenic and toxic substance. The most abundant inorganic arsenic species in water are arsenite (As(III)) and arsenate (As(V)). The type and distribution of arsenic is determined by the pH of the water, its redox potential, and the presence of complex ions such as sulfur, iron and calcium. Many people have faced the risk of arsenic poisoning due to naturally occurring groundwater arsenic pollution in many regions of the world. For this reason, Aqualine Arsenic Filter Systems solutions that we produce are used and applied with great success in reducing the arsenic values from 50µg/L, which is the previous value allowed by the World Health Organization (WHO), to below 10µg/L. 

    Since human health is prioritized in Aqualine filtration systems, the minerals used in our systems comply with world food norms.


     

    TECHNICIAL SPECIFICATIONS

    With epoxy painted carbon steel tank
    Maximum working pressure 6 bar
    Time-controlled backwash
    Butterfly valves with pneumatic actuation (Optional Electric Actuator option)                                       
    F-1215 and F-1615 sub-collection structure octopus diffuser 
    Between F-2015 and F-2815, sub-collection structure, mushroom diffuser on the mirror    
    PVC-U material surface piping (Optional galvanized surface piping option)
    Sample taps and manometers at system inlets and outlets 
    PLC based Siemens logo control panel (Optional touch screen option)
    Electricity 220V /50 Hz / 1 pH
    The supply of dry instrument air required for the operation of the pneumatic valves belongs to the customer. Recommended compressor capacity is minimum 100 Lt/min @ 8 bar.
     
     
    Within our company, Metal Tanks can be produced for Purification systems in accordance with Pressure Equipment Standards and certified.

    AD 2000 MERKBLATT
    ASME SEC.VIII 
    EN 13445 (certified by TÜV NORD SYSTEMS NOTIFIED BODY NUMBER 0045)